Resistance Temperature Detector (Rtd) Input Type (Init > Inpt > Rtd); Thermistor Input Type Configuration (Init > Inpt > Thrm) - Newport Pt32 Operator's Manual

Temperature, process and strain controllers, platinum series
Table of Contents

Advertisement

PLATINUM Series Controllers User's Guide
6.1.2 Resistance Temperature Detector (RTD) Input Type (INIt > INPt >
Rtd)
Select Rtd as the input type. Factory default configuration settings are three-wire, 100 Ω,
using the European standard 385 curve. Note that the 392 and 3916 curves are only available
for 100 Ω RTDs. If Rtd is selected and a specific configuration is not changed, the last saved
configuration will be used.
Navigate to the desired configuration parameter:
N.wIR – Firmware selection of the number of wires for RTD connection (no jumpers
needed)
A.CRV – Calibration curve covering both the international standard and the
resistance of the RTD
Select the option.
Navigate to the desired setting. Settings include the following:
Select the indicated option.
Navigate to the desired setting. Settings include the following:
Select the indicated option.
6.1.3 Thermistor Input Type Configuration (INIt > INPt > tHRM)
Select Thermistor (tHRM) as the input type. This sets up the unit for thermistor-based
temperature measurement and then the specific thermistor type can be specified. If no
thermistor type is specified, the last selected type is used.
Navigate to the correct setting. Settings include the following:
2.25k – 2,250 Ω thermistor (factory default)
5k
– 5,000 Ω thermistor
10k – 10,000 Ω thermistor
Select the indicated option.
6.1.2.1 Number of RTD Wires (INIt > INPt > Rtd >
N.wIR)
3 wI – Three-wire RTD (factory default)
4 wI – Four-wire RTD
2 wI – Two-wire RTD
6.1.2.2 Calibration Curve (INIt > INPt > Rtd > A.CRV)
385.1 – European and most common standard at the conventional
resistance of 100 Ω (factory default)
385.5 – European curve for 500 Ω
385.t – European curve for 1000 Ω
392
– Old US standard (rarely used), at 100 Ω only
3916 – Japanese standard, at 100 Ω only
Reference Section: Initialization Mode (INIt)
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pt16Pt8dPt16dPt8ePt8pt

Table of Contents