Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

December 2014
2. Feed the sensor wiring cable into the transmitter wiring compartment.
Figure 2-6:
Sensor wiring feedthrough
3. Connect the sensor wires to the appropriate terminals.
Note
Terminate the 4-wire cable drain wires only at the sensor/core processor end of the cable. See
the sensor installation manual for more detail. Do not connect the 4-wire cable drain wires to
the ground screw located inside the 5700 junction box.
See
See
Quick Installation Guide
Figure 3
for 4-wire terminal connections.
Figure 4
for 9-wire terminal connections.