Figure 1: Recommended Clearances Around The Megav2 250 Ups; Table 1: Recommended Clearances - Gamatronic MEGA V2 250 Installation Manual

Modular ups system up to 250 kw
Table of Contents

Advertisement

Front
100 cm (39 in.)
30 cm (12 in.)
Sides
60 cm (24 in)
Rear
42 cm (17.5 in.)

Figure 1: Recommended clearances around the MegaV2 250 UPS

6.
It is recommended that the battery cabinets be located as close to the UPS as is practically
possible.
4
G
AMATRONIC

Table 1: Recommended clearances

R
ECOMMENDED MINIMUM CLEARANCE AROUND THE
Clearance for user access and service.
Clearance for service; the UPS is not next to another UPS.
If there is another UPS at the side of the MegaV2, the recommended
clearance increases to 60 cm, due to the additional heat generated by
the second UPS. However, in the case that the two UPSs are being
operated in "A+B" mode, where each UPS operates at no more than
50 % capacity, 40 cm clearance (16 in.) is sufficient.
Clearance for cable connections.
E
I
L
.
LECTRONIC
NDUSTRIES
TD
MegaV2 250 Installation Guide, Release 2.2