12.2.7 Example COMMREQ Data Block for
Configuring Serial I/O Protocol
Values
FFF0H
005
0 = Slave
4=4800, 5=9600, 6=19200, 7=
38400*, 8=57600**
*CPU models IC200CPU005
and CPUE05 only
0 = None, 1 = Odd, 2 = Even
0 = Hardware, 1 = None
0-255 (units of 10ms,e.g. 10=
100ms)
0 = Long
0=7 bits, 1=8 bits
0 = 1 stop bit, 1 = 2 stop bits
not used
0 = 2-wire, 1 = 4-wire
not used
0-255 (units of 10ms,e.g. 10=100ms)
0-255 (units of 10ms,e.g. 10=100ms)
Note The data block length (Address + 0) for a COMMREQ that includes the Receive to
transmit delay and RTS drop delay should be 12H not 10H. Both forms (Length 10H and
12H) are supported.
Note If Serial I/O is configured for 115.2K baud. a major error code 12 (0cH) and a
minor error code 2 (02H) is returned in the COMMREQ status word. This will occur for
any unsupported baud rate.
Meaning
Reserved for COMMREQ use.
Command
Protocol: 0005=Serial IO
Port Mode
Data Rate
Parity
Flow Control
Turnaround Delay
Timeout
Bits per Character
Stop Bits
Interface
Duplex Mode
Device Identifier
Receive to transmit
delay
RTS drop delay