Commreq Function Block And Command Block; The Commreq Function Block - GE RX3i User Manual

Pacsystems
Hide thumbs Also See for RX3i:
Table of Contents

Advertisement

COMMREQ Function Block and Command Block

9.2
This section describes the programming structures common to all Communications Requests: the COMMREQ
Function Block and the Command Block.

The COMMREQ Function Block

The Communications Request is triggered when the logic program passes power to the COMMREQ Function
Block.
(Enable ) -------------
(Command Block address)
(Rack/Slot Location of
the Ethernet Interface)
(Task value)
Each of the inputs and outputs are discussed in detail below. It is important to understand that the Command
Block address points to the location in memory you have setup as the Command Block.
Enable: Control logic for activating the COMMREQ Function Block. See Section 5 for tips on developing your
program.
IN: The location of the Command Block. It can be any valid address within a word-oriented area of memory
(%R, %AI, %AQ, %P, %L or %W for the Ethernet interface).
SYSID: A hexadecimal word value that gives the rack (high byte) and slot (low byte) location of the Ethernet
interface. For the PACSystems embedded Ethernet interface, enter the rack/slot location of the module.
Examples:
Rack
Slot
Hex Word Value
0
0
16#0001
0
1
16#0001
0
4
16#0004
3
4
16#0304
2
10
16#020A
4
2
16#0402
TASK: For the RX3i and Rx7i ETM001 Ethernet interfaces TASK must always be set to zero. For PACSystems CPU
embedded Ethernet interface, TASK must be set to 65536 (0x10000) to address the CPU's Ethernet
daughterboard.
Caution notices are used where equipment might be damaged if care is
not taken.
GFK-2224Q
COMM
REQ
IN
FT
-
SYSID
-
TASK
-
Figure 56: The COMMREQ Function Block
Notes
RXi and CPE400
Slot 1 is used for the Ethernet daughterboard on an RX7i CPU.
January 2017
Chapter 9. Modbus/TCP Client
- Function Faulted (logic)
Caution
143

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx7i

Table of Contents