GE VersaMax PLC User Manual page 90

Table of Contents

Advertisement

Description
Name
Transfer/Response timeout value (in
crsp_tout
seconds)
ARP cache timeout interval (in seconds)
fflush
UDP port for Ethernet Global Data control
gctl_port
messages
UDP port for point-to-point Ethernet Global
gdata_port
Data messages
IP time-to-live for global broadcast messages
gbcast_ttl
(hop count)
IP time-to-live for point-to-point messages
gucast_ttl
(hop count)
gXX_udp
UDP port for host group XX
IP time-to-live for host group (multicast)
gXX_ttl
messages (hop count)
IP group address for host group XX (must be
gXX_addr
class D address)
IP header default time-to-live (hop count)
ittl
ifrag_tmr
IP fragment timeout interval (in seconds)
wnodelay
TCP nodelay option (0=inactive, 1=active)
wkal_idle
TCP keepalive timer value (in seconds)
wkal_cnt
TCP keepalive probe count
wkal_intvl
TCP keepalive probe interval (in seconds)
TCP maximum segment lifetime (in seconds)
wmsl
wsnd_buf
TCP send buffer size in bytes
wrcv_buf
TCP receive buffer size in bytes
NTP min. poll interval for host 1. The value
specifies log(2) of the interval in seconds (eg:
nmin_poll1
the value 3 means 8 secs, 4 means 16 sec,
etc)
NTP maximum poll interval for host 1 (in log
nmax_poll1
(2) of seconds)
NTP min. poll interval for host 2 (in log(2) of
nmin_poll2
seconds)
NTP max. poll interval for host 2 (in log(2) of
nmax_poll2
seconds)
NTP min. poll interval for host 3 (in log(2) of
nmin_poll3
seconds)
NTP max. poll interval for host 3 (in log(2) of
nmax_poll3
seconds)
90
GFK-1503E
For public disclosure
Range
Default
16 (0010H)
10 – 3600 (0e10H)
0 – 604800 (93a80H)
600 (0258H)
7937 (1f01H)
0-65535 (ffffH)
18246 (4746H)
0-65535 (ffffH)
1 (1H)
0-255 (00ffH)
16 (10H)
0-255 (00ffH)
18246 (4746H)
0-65535 (ffffH)
1 (1H)
0-255 (00ffH)
224.0.0.2 -
224.0.7.XX
239.255.255.255
64 (0040H)
0-255 (00ffH)
3 (0003H)
0-65535 (ffffH)
0 (000H)
0,1
240 (00f0H) = 4.0
minutes
2 (0002H)
0-65535 (ffffH)
60 (003cH)
30 (001eH)
4096 (1000H)
0-32767 (7fffH)
4096 (1000H)
6 (0006H) = 64 seconds
4 – 14 (000eH)
10 (000aH) = 1024 sec.
(16 – 16384 sec)
6 (0006H) = 64 sec.
10 (000aH) = 1024 sec.
6 (0006H) = 64 sec.
10 (000aH) = 1024 sec.
VersaMax PLC User Manual