4.3.3 Connecting the Expansion Cable: RS-485
Differential
For a multiple-rack expansion system, connect the cable from the expansion port on the
Expansion Transmitter to the Expansion Receivers as shown below. If all the Expansion
Receivers are the Isolated type (IC200ERM001), the maximum overall cable length is
750 meters. If the expansion bus includes any non-isolated Expansion Receivers
(IC200ERM002), the maximum overall cable length is 15 meters.
VersaMax PLC or I/O Station Main Rack (0)
ETM
PS
CPU/NIU
VersaMax ExpansionRack 1
PS
15M with any
IC200ERM002 ERMs
750M with all
IC200ERM001 ERMs
ERM
VersaMax ExpansionRack 7
PS
Terminator
Plug
ERM
Install the Terminator Plug (supplied with the Expansion Transmitter module) into the
lower port on the last Expansion Receiver. Spare Terminator Plugs can be purchased
separately as part number IC200ACC201 (Qty 2).
4.3.4 RS-485 Differential Inter-Rack Connection
(IC200CBL601, 602, 615)

4.3.5 Building a Custom Expansion Cable

Custom expansion cables can be built using Connector Kit IC200ACC202, Crimper AMP
90800-1, and Belden 8138, Manhattan/CDT M2483, Alpha 3498C, or equivalent AWG
#28 (0.089mm
2
) cable.