3.3 VersaMax General Product Specifications

Environmental
Vibration
Shock
Operating Temp.
Storage Temp.
Humidity
Enclosure Protection
EMC Emission
Radiated, Conducted
EMC Immunity
Electrostatic Discharge
RF Susceptibility
Fast Transient Burst
Surge Withstand
Conducted RF
Isolation
Dielectric Withstand
Power Supply
Input Dips, Variations
42
GFK-1503E
For public disclosure
VersaMax products should be installed and used in conformance with product-specific
guidelines as well as the following specifications:
IEC60068-2-6
IE600C68-2-27
IEC60529
CISPR 11/EN 55011
CISPR 22/EN 55022
FCC 47 CFR 15
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
ANSI/IEEE C37.90a
EN 61000-4-18
IEC60255-4
EN 61000-4-5
EN 61000-4-6
UL508, UL840,
IEC664
EN 61000-4-11
1G @57-150Hz, 0.012in p–p @10-57Hz
15G, 11ms
0°C (32 °F) to +60°C (140 °F) ambient
-40°C (-40 °F) to +85°C (185 °F)
5% to 95%, noncondensing
Steel cabinet per IP54:
protection from dust & splashing water
Industrial Scientific & Medical Equipment
(Group 1, Class A)
Information Technology Equipment (Class A)
referred to as FCC part 15,
Radio Devices (Class A)
8KV Air, 4KV Contact
10Vrms /m, 80Mhz to 1000Mhz, 80% AM
2KV: power supplies, 1KV: I/O, communication
Damped Oscillatory Wave: 2.5KV power supplies,
I/O [12V-240V]; 1KV communication
Damped Oscillatory Wave: Class II,
power supplies, I/O [12V-240V]
2 kV cm(P/S); 1 kV cm (I/O and communication modules)
10Vrms, 0.15 to 80Mhz, 80%AM
1.5KV
During Operation: Dips to 30% and 100%, Variation for AC
+/-10%, Variation for DC +/-20%