GE VersaMax PLC User Manual page 148

Table of Contents

Advertisement

MOVE
Enable
BOOL
9
IN
Input/
Output
enable
Length
IN
ok
Q
148
GFK-1503E
For public disclosure
The result of the Move depends on the data type selected for the function, as shown
below. For example, if the constant value 9 is specified for IN and the length is 4, then 9
is placed in the bit memory location specified by Q and the three locations following:
MOVE_BOOL
OK
Q
Output
msb
lsb
1 0 0 1
(Length = 4 bits)
The function passes power to the right whenever power is received.
10.3.1.1 Parameters for the Move Data Function
Choices
When the function is enabled, the move is performed.
flow
The number of bits, words, or double words of data to be
copied. This is the length of IN. Length must be from 1 to 256
for all types except BIT. If IN is a constant and Q is type BIT,
the length must be between 1 and 16. If IN is type Bit, the
length must be between 1 and 256 bits.
I, Q, M, T, G,
IN contains the value to be moved. For MOVE_BOOL, any
R, AI, AQ,
discrete reference may be used; it does not need to be byte
constant
aligned. However, 16 bits, beginning with the reference
For bit or word
address specified, are displayed online.
data only: S
For real data:
R, AI, AQ
The OK output is energized whenever the function is
flow, none
enabled.
I, Q, M, T, G,
When the move is performed, the value at IN is written to Q.
R, AI, AQ,
For MOVE_BOOL, any discrete reference may be used; it
For bit/ word
does not need to be byte aligned. However, 16 bits,
data: SA, SB,
beginning with the reference address specified, are displayed
SC
online.
For real data:
R, AI, AQ
MOVE_INT
MOVE
Enable
OK
INT
9
IN
Q
Output
(Length = 4 words)
Description
9
9
9
9
VersaMax PLC User Manual