15 The EZ Program Store Device

Connector
The EZ Program Store Device
For public disclosure
This chapter describes the VersaMax EZ Program Store device (IC200ACC003), which
can be used to transfer program, configuration, and reference tables data from one PLC to
one or more others of the same type.
IC200ACC003
PLC
Contents of this chapter:
Description of the EZ Program Store device
Details of Using the EZ Program Store device
Read/Write/Verify Data with a Programmer Present
Write Data to a PLC CPU without a Programmer Present
The EZ Program Store device (IC200ACC003) can be used to store and update the
configuration, application program, and reference tables data of a VersaMax PLC. The
update can include Ethernet Global Data and Advanced User Parameters for Ethernet. A
programmer and PLC CPU are used to initially write data to the device. In addition to
writing data to the device, the programmer can read data already stored on an EZ Program
Store device, and compare that data with similar files already present in the programmer.
Once the data is written to the EZ Program Store device, the data can be written to one or
more other PLC CPUs of the same type, with no programmer needed.
Side
IC200ACC003
PLC
EZ PROGRAM STORE
6.6cm
2.6 in
The EZ Program Store device and PLC must both have no OEM key password or the
same OEM key password for an update to occur. The EZ Program Store device does not
perform special processing for other types of passwords.
Green
OK
Amber
Active
EZ PROGRAM STORE
Blink
Error
Pushbutton
Green
OK
Amber
5.8cm
Active
1.7 in
Blink
Error
Top
LED
1.8cm
0.7 in
GFK-1503E User Manual 293