Vega VEGAPULS 62 Operating Instructions Manual page 64

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 62:
Table of Contents

Advertisement

9 Diagnosis, asset management and service
Measurement error with constant level
Fault description
1. Measured value
shows a too low or too
high level
2. Measured value
jumps towards 0 %
3. Measured value
jumps towards 100 %
Measurement error during filling
Fault description
4. Measured value re-
mains unchanged
during filling
5. Measured value re-
mains in the bottom
section during filling
6. Measured value re-
mains momentarily
unchanged during fill-
ing and then jumps to
the correct level
64
Error pattern
Reason
Min./max. adjustment not
correct
Incorrect linearization curve
0
time
Installation in a bypass tube or
standpipe, hence running time
error (small measurement error
close to 100 %/large error close
to 0 %)
Multiple echo (vessel top,
product surface) with amplitude
higher than the level echo
0
time
Due to the process, the ampli-
tude of the level echo sinks
A false signal suppression was
not carried out
0
time
Amplitude or position of a false
signal has changed (e.g. con-
densation, buildup); false signal
suppression no longer matches
actual conditions
Error pattern
Reason
False signals in the close range
too big or level echo too small
Strong foam or spout generation
Max. adjustment not correct
0
time
Echo from the tank bottom
larger than the level echo, for
example, with products with
ε
< 2.5 oil-based, solvents
r
0
time
Turbulence on the product
surface, quick filling
0
time
Removal
Adapt min./max. adjustment
Adapt linearization curve
Check parameter "Application"
with respect to vessel form,
adapt if necessary (bypass,
standpipe, diameter)
Check parameter "Application",
especially vessel top, type of
medium, dished bottom, high
dielectric constant, and adapt if
necessary
Carry out a false signal suppres-
sion
Determine the reason for the
changed false signals, carry out
false signal suppression, e.g.
with condensation
Removal
Eliminate false signals in the
close range
Check measurement situation:
Antenna must protrude out of
the socket, installations
Remove contamination on the
antenna
In case of interferences due to
installations in the close range:
Change polarisation direction
Create a new false signal sup-
pression
Adapt max. adjustment
Check parameters Medium,
Vessel height and Floor form,
adapt if necessary
Check parameters, change if
necessary, e.g. in dosing vessel,
reactor
VEGAPULS 62 • 4 ... 20 mA/HART - four-wire