Code
Text message
F260
Error in the calibration
F261
Error in the instrument set-
tings
F264
Installation/Setup error
F265
Measurement function dis-
turbed
Function check
Out of specification
VEGAPULS 62 • 4 ... 20 mA/HART - four-wire
Reason
•
Error in the calibration
carried out in the factory
•
Error in the EEPROM
•
Error during setup
•
False signal suppression
faulty
•
Error when carrying out
a reset
•
Adjustment not within the
vessel height/measuring
range
•
Max. measuring range
of the instrument not
sufficient
•
Sensor no longer carries
out a measurement
•
Operating voltage too
low
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Code
Text message
C700
Simulation active
The following table shows the error codes and text messages in the
status message "Out of specification" and provides information on
causes as well as corrective measures.
Code
Text message
S600
Impermissible
electronics tem-
perature
S601
Overfilling
9 Diagnosis, asset management and service
Removal
•
Exchanging the electron-
ics
•
Send instrument for
repair
•
Repeat setup
•
Carry out a reset
•
Check or correct instal-
lation and/or parameter
adjustment
•
Use an instrument with
bigger measuring range
•
Check operating voltage
•
Carry out a reset
•
Disconnect operating
voltage briefly
Reason
Removal
•
•
A simulation is
Finish simula-
active
tion
•
Wait for the
automatic end
after 60 mins.
Reason
Removal
•
•
Temperature of
Check ambient
the electronics
temperature
•
in the non-
Isolate electron-
specified range
ics
•
Use instrument
with higher tem-
perature range
•
•
Danger of ves-
Make sure
sel overfilling
that there is no
further filling
•
Check level in
the vessel
DevSpec State in CMD
48
Bit 8 of Byte 0 ... 5
Bit 9 of Byte 0 ... 5
Bit 10 of Byte 0 ... 5
Bit 11 of Byte 0 ... 5
DevSpec State
in CMD 48
"Simulation
Active" in "Stand-
ardized Status 0"
DevSpec State
in CMD 48
Bit 5 of
Byte 14 ... 24
Bit 6 of
Byte 14 ... 24
61