Vega VEGAPULS 62 Operating Instructions Manual page 18

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 62:
Table of Contents

Advertisement

4 Mounting
Sensor orientation
18
Fig. 12: Deviating socket dimensions
Socket diameter d
40 mm
50 mm
80 mm
100 mm
150 mm
Socket diameter d
1½"
2"
3"
4"
6"
Tip:
The instrument is also optionally available with an antenna extension.
The antenna length can be selected (either ex works or later) to allow
the antenna to protrude slightly out of the end of the mounting socket.
Due to the antenna extension however, disturbing reflections are
generated in the close-up range. This can lead to an increase in the
required minimum distance, especially with poorly reflecting media
such as plastic powder. In practice, a cleanly constructed mounting
socket, if necessary with rounded edges, introduces fewer disturbing
influences than an antenna extension.
In liquids, direct the sensor as perpendicular as possible to the prod-
uct surface to achieve optimum measurement results.
Fig. 13: Alignment in liquids
d
Socket length h
≤ 100 mm
≤ 150 mm
≤ 250 mm
≤ 500 mm
≤ 800 mm
Socket length h
≤ 3.9 in
≤ 5.9 in
≤ 9.8 in
≤ 19.7 in
≤ 31.5 in
VEGAPULS 62 • 4 ... 20 mA/HART - four-wire
Recommended anten-
na diameter
40 mm
48 mm
75 mm
95 mm
95 mm
Recommended anten-
na diameter
1½"
2"
3"
4"
4"