Quick Start - Baldor VS1SM Installation & Operating Manual

Single phase ac drive
Table of Contents

Advertisement

1.3

Quick Start

VS1SM80P5/80P5-F, VS1SM81/81-F
L1
L2
Powerup Procedure
1.
Remove all power from the control.
2.
Connect Power & Motor, See Figure 1‐1.
3.
Connect input control wires and output wires, See Figure 1‐2.
4.
Disconnect the motor from the load (including coupling or inertia wheels).
5.
Turn power on. Be sure there are no faults.
6.
Set the following parameters for the values displayed on the motor nameplate:
P30 Motor HP Select
P32 Motor Rated Current
P33 Pole Number
P34 Base Frequency
7.
If external dynamic brake hardware is used, set the Level 2 Brake Adjust block "Resistor Ohms"
and "Resistor Watts" parameters.
WARNING:
The motor shaft will rotate during this procedure. Be certain that unexpected motor
shaft movement will not cause injury to personnel or damage to equipment.
8.
Set H41 =1 from using the Keypad. Perform each step including auto tune.
9.
Remove all power from the control.
10. Couple the motor to its load.
11. Verify freedom of motion of motor shaft.
12. Verify the motor coupling is tight without backlash.
13. Verify the holding brakes if any, are properly adjusted to fully release and set to the desired torque.
14. Turn power on. Be sure no errors are displayed.
15. Run the drive from the keypad.
16. Select and program additional parameters to suit your application, see Chapter 8.
The control is now ready for use the in keypad mode. If a different operating mode is desired, refer to
Chapter 7 Parameter Descriptions and Chapter 8 Customizing for your Application.
MN760
Quick Start Guide is also available separately, see MS760.
Figure 1‐1 Power & Motor Terminal Locations
Jumper Bar
P
P1
N
U
V
W
Refer to Chapter 3, 4 and 5 for additional details.
VS1SM82/82-F, VS1SM83/83-F
L1
L2
P
Jumper Bar
P1
N
U
V
Quick Start 1-3
W

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vs1sm80p5Vs1sm81Vs1sm82

Table of Contents