7.3 Function Group2
Parameter #
MN761
Continued
Access
Parameter Name, Value Range, Description and Preset Value
RW
I Gain During Speed Search (Range: 0-9999)
Sets the PI Controller Integral Gain used during Speed Search.
Preset Value:
RW
Restart Attempts (Range: 0-10)
Sets the number of Auto-Restarts allowed after faults occur. Helps prevent
the system from going down due to internal protection function activated
by causes such as noise.
Preset Value:
RW
Auto-Restart Time (Range: 0-60sec)
Sets the time between Auto-Restart attempts
Preset Value:
RW
Motor Type Selection (Range:
0.2=
0.4=
0.75=
1.5=
2.2=
Sets the type of motor.
Preset Value:
RW
Motor Poles (Range: 2-12)
Sets the number of motor poles.
Preset Value:
RW
Slip Frequency (Range: 0-10Hz)
Sets the motor Slip Frequency (f
motor poles (P).
Preset Value:
* RPM x P
+ f
f
s
r
RW
Motor Rated Current (Range: 0.5-50A)
Sets the rated motor current. See the motor nameplate.
Preset Value:
RW
No Load Motor Current (Range: 0.1-20A)
Sets the motor current as measured when the motor is rotating at rated
RPM with no load (approximately 50% of the motor rated current).
Preset Value:
RW
Motor Efficiency (Range: 50-100%)
Sets the motor efficiency. See the motor nameplate.
Preset Value:
1000
0
1.0
0.2kW
0.4kW
0.75kW
1.5kW
2.2kW)
CALC
CALC
) based on Rated frequency (f
s
CALC
120
CALC
11
87
), RPM and
r
Parameter Descriptions 7-13