7.2
Function Group1
Parameter #
MN761
Access
Parameter Name, Value Range, Description and Preset Value
RW
Jump Code (Range: 0-60)
Sets the parameter number to jump to within Function Group1.
Allows quick access to a desired parameter.
Preset Value:
RW
Forward/Reverse Run Disable (Range:
0- Forward and reverse run enabled
1- Forward run disabled
2- Reverse run disabled)
Enables or disables the ability to run the drive in forward or reverse.
Preset Value:
RW
Accel Pattern F02, Decel Pattern F03 (Range:
0- Linear. A general pattern for constant torque applications.
1- S-Curve. Allows the motor to accelerate and decelerate smoothly.)
If set to S-Curve, the actual accel time will take longer than the time set by
the user, as illustrated here.
If H70 is set to maximum speed and target speed is set to less than
maximum speed, the shape of S-curve may be distorted.
Preset Value:
Freq.
Run
Stop Mode (Range:
RW
0- Decelerate to stop. Decels to 0Hz for the preset time.
1- DC Brake to stop. See Chapter 8 for information.
2- Free run to stop. Motor output is disabled and motor coasts to stop.)
Preset Value:
Freq.
Run
1
0
F02=0, F03=0
Linear
Accel
0
Decel
S- Curve
Decel
Freq.
Run
Parameter Descriptions 7-3