7.2 Function Group1
Parameter #
MN761
Continued
Access
Parameter Name, Value Range, Description and Preset Value
RW
Start Speed (Range: 0.1-10Hz)
Sets initial speed of the inverter.
Preset Value:
RW
Speed High/Low Limit Selection (Range: 0=No, 1=Yes)
Sets whether the high/low limits (F25 and F26) are used.
Preset Value:
RW
Speed High Limit (Range: 0-400Hz)
Sets the upper speed limit. Cannot be greater than F21.
Preset Value:
RW
Speed Low Limit (Range: 0.1-400Hz)
Sets the lower speed limit. Cannot be greater than F25 or less than F23.
Preset Value:
RW
Torque Boost (Range:
0- Manual. Torque levels set in F28 and F29 are used.
1- Auto. Automatically boosts the output voltage by calculated torque boost
value using motor parameters.
Sets how Torque Boost is applied.
Preset Value:
RW
Forward Torque Boost (Range: 0-15%)
Sets the torque boost level during forward run.
Excess boost may cause motor overheating.
Preset Value:
FWD Tq Boost
REV Tq Boost
FWD
REV
RW
Reverse Torque Boost (Range: 0-15%)
Sets the torque boost level during reverse run.
Excess boost may cause motor overheating.
Preset Value:
0.50
0
60.00
Parameter is only displayed when F24 =1.
0.50
Parameter is only displayed when F24 =1.
0
5
Voltage
100%
5
No torque boost
Time