PARAMETERS MENU
Table 34: Feedback settings
Index
Parameter
P3.12.3.1
Feedback Function
Feedback Function
P3.12.3.2
Gain
Feedback 1 Source
P3.12.3.3
Selection
P3.12.3.4
Feedback 1 Minimum
Feedback 1 Maxi-
P3.12.3.5
mum
Feedback 2 Source
P3.12.3.6
Selection
P3.12.3.7
Feedback 2 Minimum
Feedback 2 Maxi-
M3.12.3.8
mum
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
1
9
-1000.0
1000.0
%
0
14
-200.00
200.00
%
-200.00
200.00
%
0
14
-200.00
200.00
%
-200.00
200.00
%
Default
ID
Description
1 = Only Source1 in use
2 = SQRT(Source1);
(Flow=Constant x
SQRT(Pressure))
3 = SQRT(Source1-
Source 2)
4 = SQRT(Source 1) +
SQRT (Source 2)
1
333
5 = Source 1 + Source 2
6 = Source 1 - Source 2
7 = MIN (Source 1,
Source 2)
8 = MAX (Source 1,
Source 2)
9 = MEAN (Source 1,
Source 2)
100.0
1058
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
2
334
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
0.00
336
100.00
337
See P3.12.3.3.
0
335
0.00
338
See P3.12.3.4.
See P3.12.3.5.
100.00
339
VACON · 81