Vacon 100 hvac Applications Manual page 159

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

PARAMETER DESCRIPTIONS
VACON · 159
P3.9.19 RESPONSE TO FIELDBUS COMMUNICATION FAULT (ID 733)
Use this parameter to select the response of the drive to a 'Fieldbus Timeout' fault.
If the data connection between the master and the fieldbus board is defective, a fieldbus fault
occurs.
P3.9.20 SLOT COMMUNICATION FAULT (ID 734)
Use this parameter to select the response of the drive to a 'Slot Communication' fault.
If the drive detects a defective option board, a slot communication fault occurs.
See P3.9.2 for more information.
P3.9.21 THERMISTOR FAULT (ID 732)
Use this parameter to select the response of the drive to a 'Thermistor' fault.
If the thermistor detects too high temperature, a thermistor fault occurs.
See P3.9.2 for more information.
P3.9.22 RESPONSE TO PID1 SUPERVISION FAULT (ID 749)
Use this parameter to select the response of the drive to a 'PID Supervision' fault.
If the PID feedback value is not in the supervision limits for longer than the supervision delay,
a PID supervision fault occurs.
P3.9.23 RESPONSE TO EXTERNAL PID SUPERVISION FAULT (ID 757)
Use this parameter to select the response of the drive to a 'PID Supervision' fault.
If the PID feedback value is not within the supervision limits for longer than the supervision
delay, a PID supervision fault occurs.
See P3.9.2 for more information.
P3.9.25 TEMPERATURE SIGNAL 1 (ID 739)
Use this parameter to select the temperature input signals that are supervised.
The maximum value is taken from the set signals and used for alarm and fault triggering.
P3.9.26 ALARM LIMIT 1 (ID 741)
Use this parameter to set the temperature alarm limit.
If the measured temperature goes above this limit, a temperature alarm occurs.
P3.9.27 FAULT LIMIT 1 (ID 742)
Use this parameter to set the temperature fault limit.
If the measured temperature goes above this limit, a temperature fault occurs.
P3.9.28 TEMP FAULT RESPONSE (ID 740)
Use this parameter to select the response of the drive to 'Temperature' fault.
10
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM

Advertisement

Table of Contents
loading

Table of Contents