VACON · 140
PARAMETER DESCRIPTIONS
P3.5.1.19 TIMER 2 (ID 448)
Use this parameter to select the digital input signal that starts the timer.
The timer starts when this signal is deactivated (falling edge). The output is deactivated when
the time defined in the duration parameter has elapsed.
P3.5.1.20 TIMER 3 (ID 449)
Use this parameter to select the digital input signal that starts the timer.
The timer starts when this signal is deactivated (falling edge). The output is deactivated when
the time defined in the duration parameter has elapsed.
P3.5.1.21 DISABLE TIMER FUNCTION (ID 1499)
Use this parameter to select the digital input signal that enables/disables all timer functions.
P3.5.1.22 PID1 SETPOINT BOOST (ID 1046)
Use this parameter to set the digital input signal that selects the PID setpoint value to be
used.
P3.5.1.23 PID1 SETPOINT SELECTION (ID 1047)
Use this parameter to set the digital input signal that selects the PID setpoint value to be
used.
P3.5.1.24 PID2 START SIGNAL (ID 1049)
Use this parameter to select the digital input signal that starts and stops the external PID
controller.
P3.5.1.25 PID2 SETPOINT SELECTION (ID 1048)
Use this parameter to set the digital input signal that selects the PID setpoint value to be
used.
P3.5.1.26 MOTOR 1 INTERLOCK (ID 426)
Use this parameter to select the digital input signal that is used as interlock signal for the
Multi-pump system.
P3.5.1.27 MOTOR 2 INTERLOCK (ID 427)
Use this parameter to select the digital input signal that is used as interlock signal for the
Multi-pump system.
P3.5.1.28 MOTOR 3 INTERLOCK (ID 428)
Use this parameter to select the digital input signal that is used as interlock signal for the
Multi-pump system.