MONITORING VALUE DESCRIPTIONS
V2.2.12 MOTOR TEMPERATURE (ID 9)
This monitoring value shows the calculated motor temperature in percentage of the nominal
working temperature.
When the value rises above 105%, motor thermal protection fault occurs.
V2.2.13 ANALOGUE INPUT 1 (ID 59)
This monitoring value shows the value of the analogue input signal as a percentage of the
used range.
V2.2.14 ANALOGUE INPUT 1 (ID 60)
This monitoring value shows the value of the analogue input signal as a percentage of the
used range.
V2.2.15 ANALOGUE OUTPUT 1 (ID 81)
This monitoring value shows the value of the analogue output as a percentage of the used
range.
V2.2.16 MOTOR PREHEAT (ID 1228)
This monitoring value shows the status of the motor preheat function.
V2.2.17 DRIVE STATUS WORD (ID 43)
This monitoring value shows the bit-coded status of drive.
V2.2.19 FIRE MODE STATUS (ID 1597)
This monitoring value shows the status of the Fire mode function.
V2.2.20 DIN STATUS WORD 1 (ID 56)
This monitoring value shows the bit-coded status of the digital input signals.
A 16 bit word, where each bit shows the status of 1 digital input. 6 digital inputs from each
slot are read. Word 1 starts from the input 1 in slot A (bit0) and ends with input 4 in slot C
(bit15).
V2.2.21 DIN STATUS WORD 2 (ID 57)
This monitoring value shows the bit-coded status of the digital input signals.
A 16 bit word, where each bit shows the status of 1 digital input. 6 digital inputs from each
slot are read. Word 2 starts from the input 5 in slot C (bit0) and ends with input 6 in slot E
(bit13).
V2.2.22 MOTOR CURRENT WITH 1 DECIMAL (ID 45)
This monitoring value shows the measured current of the motor with the fixed number of
decimals and that is less filtered.