QUICK STARTUP GUIDE
From Standard I/O board
From term.
From term.
#6 or 12
#13
RUN
Fig. 5: The control connection example for the relay board 1
NOTE!
Not available for Vacon 100 X.
From Standard I/O board
From term.
From term.
#12
#13
RUN
Fig. 6: The control connection example for the relay board 2
NOTE!
The only option for Vacon 100 X.
You can also isolate the digital inputs (terminals 8-10 and 14-16) on the standard I/O board
from ground. To do this, set the dip switch on the control board to position OFF. See the
figure below to find the switches and to make applicable selections for your requirements.
NOTE!
For the DIP switch configurations in Vacon 100 X, see the Vacon 100 X Installation
manual.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Relay board 1
Terminal
21
RO1/1 NC
22
RO1/2 CM
RO1/3 NO
23
24
RO2/1 NC
25
RO2/2 CM
26
RO2/3 NO
32
RO3/1 CM
33
RO3/2 NO
Relay board 2
Terminal
21
RO1/1 NC
22
RO1/2 CM
23
RO1/3 NO
24
RO2/1 NC
25
RO2/2 CM
26
RO2/3 NO
28
TI1+
29
TI1-
Default
Signal
Relay output 1
Relay output 2
FAULT
Relay output 3
READY
Default
Signal
Relay output 1
Relay output 2
FAULT
Thermistor input
VACON · 15
RUN
RUN
1