Vacon 100 hvac Applications Manual page 123

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

PARAMETER DESCRIPTIONS
9. The STOP button on the keypad is
pushed and the frequency that is fed to
the motor goes to 0. (This signal only
works if the value of P3.2.3 Keypad Stop
Button is Yes.)
10. The drive starts because the START
button on the keypad was pushed.
Selection
Selection name
number
CS1 = Start (edge)
4
CS2 = Reverse
FWD
Output
frequency
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad stop
button
1
2
Fig. 19: I/O A Start/stop logic = 4
1. Control signal (CS) 1 activates and
causes the output frequency to increase.
The motor operates forward because
CS2 is inactive.
2. CS2 activates, which causes the
direction to start to change (FWD to
REV).
3. CS2 becomes inactive, which causes the
direction to start to change (REV to
FWD), because CS1 is still active.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
11. The drive is stopped again with the STOP
button on the keypad.
12. The attempt to start the drive with the
START button is not successful, because
CS1 is inactive.
Use this function to prevent an accidental start. Before you
can start the motor again, you must open the start/stop con-
tact.
3 4
6
7
5
4. CS1 becomes inactive and the frequency
goes to 0.
5. CS2 activates, but the motor does not
start because CS1 is inactive.
6. CS1 activates and causes the output
frequency to increase again. The motor
operates forward, because CS2 is
inactive.
Description
8
9
10
VACON · 123
t
11
10

Advertisement

Table of Contents
loading