Vacon 100 hvac Applications Manual page 79

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

PARAMETERS MENU
Table 33: Setpoint settings
Index
Parameter
P3.12.2.1
Keypad setpoint 1
P3.12.2.2
Keypad setpoint 2
P3.12.2.3
Setpoint ramp time
Setpoint source 1
P3.12.2.4
selection
P3.12.2.5
Setpoint 1 minimum
P3.12.2.6
Setpoint 1 maximum
Sleep Frequency
P3.12.2.7
limit 1
P3.12.2.8
Sleep Delay 1
P3.12.2.9
Wake-up Level 1
Setpoint 1 Wake-up
P3.12.2.10
Mode
P3.12.2.11
Setpoint 1 boost
Setpoint source 2
P3.12.2.12
selection
P3.12.2.13
Setpoint 2 minimum
P3.12.2.14
Setpoint 2 maximum
Sleep Frequency
P3.12.2.15
limit 2
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
Varies
Varies
Varies
Varies
Varies
Varies
0.00
300.0
s
0
19
-200.00
200.00
%
-200.00
200.00
%
0.00
320.00
Hz
0
3000
s
-214748.
214748.
Varies
36
36
0
1
-2.0
2.0
x
0
16
-200.00
200.00
%
-200.00
200.00
%
0.00
320.00
Hz
Default
ID
Description
0
167
0
168
0.00
1068
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
1
332
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temp. Input 1
18 = Temp. Input 2
19 = Temp. Input 3
0.00
1069
100.00
1070
0.00
1016
0
1017
0
1018
0 = Absolute level
0
15539
1 = Relative setpoint
1.0
1071
See P3.12.2.4.
2
431
0.00
1073
See P.12.2.5.
100.00
1074
See P3.12.2.6.
See P3.12.2.7.
0.00
1075
VACON · 79
5

Advertisement

Table of Contents
loading

Table of Contents