QUICK STARTUP GUIDE
Table 2: Quick Setup parameter group
Index
Parameter
Motor Nominal Volt-
P1.1
age
Motor Nominal Fre-
P1.2
quency
Motor Nominal
P1.3
Speed
Motor Nominal Cur-
P1.4
rent
P1.5
Motor Cos Phi
P1.6
Motor nominal power
P1.7
Motor Current Limit
P1.8
Minimum Frequency
P1.9
Maximum Frequency
I/O Control Refer-
P1.10
ence A Selection
P1.11
Preset frequency 1
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
Varies
Varies
V
8.0
320.0
Hz
24
19200
rpm
Varies
Varies
A
0.30
1.00
Varies
Varies
kW
Varies
Varies
A
0.00
P1.9
Hz
P1.8
320.00
Hz
1
8
P3.3.1
300.00
Hz
Default
ID
Description
Find this value U
the nameplate of the
Varies
110
motor.
See P3.1.1.1.
Find this value f
the nameplate of the
50
111
motor.
See P3.1.1.2.
Find this value n
Varies
112
the nameplate of the
motor.
Find this value I
Varies
113
the nameplate of the
motor.
Find this value on the
Varies
120
nameplate of the
motor.
Find this value n
Varies
116
the nameplate of the
motor.
The maximum motor
Varies
107
current from the AC
drive.
The minimum fre-
Varies
101
quency reference that
is acceptable.
The maximum fre-
50.00
102
quency reference that
is acceptable.
The selection of the
frequency reference
source when the con-
6
117
trol place is I/O A.
See P3.3.3 for selec-
tions.
Select with the digital
input: Preset frequency
10.00
105
selection 0 (P3.5.1.15)
(Default = Digital Input
4)
VACON · 17
on
n
on
n
on
n
on
n
on
n
1

Advertisement