PARAMETER DESCRIPTIONS
With parameter P3.10.5, you can set the maximum number of automatic reset trials during
the trial time set in P3.10.4. The fault type does not have an effect on the maximum number.
Fault trigger
Alarm
Autoreset
Trial time
Fault active
Fig. 33: The Automatic reset function
P3.10.6 AUTORESET: UNDERVOLTAGE (ID 720)
Use this parameter to enable the automatic reset after an undervoltage fault.
P3.10.7 AUTORESET: OVERVOLTAGE (ID 721)
Use this parameter to enable the automatic reset after an overvoltage fault.
P3.10.8 AUTORESET: OVERCURRENT (ID 722)
Use this parameter to enable the automatic reset after an overcurrent fault.
P3.10.9 AUTORESET: AI LOW (ID 723)
Use this parameter to enable the automatic reset after a fault caused by low AI signal.
P3.10.10 AUTORESET: UNIT OVERTEMPERATURE (ID 724)
Use this parameter to enable the automatic reset after a fault caused by unit
overtemperature.
P3.10.11 AUTORESET: MOTOR OVERTEMPERATURE (ID 725)
Use this parameter to enable the automatic reset after a fault caused by motor
overtemperature.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Wait
Wait
time
time
ID717
ID717
Reset 1
Number of trials: (ID759 = 2)
Wait
time
ID717
Reset 2
Trial time
ID718
VACON · 161