VACON · 144
Table 60: The output signals through RO1
Selection
number
0
Not used
1
Ready
2
Run
3
General fault
4
General fault inverted
5
General alarm
6
Reversed
At speed
7
Motor regulator activated
8
Preset Frequency active
9
Keypad control active
10
I/O control B active
11
12
Limit supervision 1
13
Limit supervision 2
14
Start command active
15
Reserved
16
Fire mode ON
17
RTC timer 1 control
18
RTC timer 2 control
19
RTC timer 3 control
20
FB Control WordB 13
21
FB Control WordB 14
22
FB Control WordB 15
23
PID in Sleep mode
10
Selection name
The output is not used.
The AC drive is ready to operate.
The AC drive operates (the motor runs).
A fault trip occurred.
A fault trip did not occur.
The reverse command is given.
The output frequency has become the same as the set fre-
quency reference.
One of the limit regulators (for example current limit or tor-
que limit) is activated.
The selection of preset frequency was made with digital input
signals.
The selection is keypad control (the active control place is
keypad).
The selection is I/O control place B (the active control place
is I/O B).
The limit supervision activates if the signal value goes below
or above the set supervision limit (P3.8.3 or P3.8.7).
Start command is active.
Time channel 1 is in use.
Time channel 2 is in use.
Time channel 3 is in use.
PARAMETER DESCRIPTIONS
Description