The function External Fault Close, the location of which is the menu M3.5.1, is parameter
P3.5.1.11. It gets the default value DigIN SlotA.3 in the graphical display, and dI A.3 in the text
display. After this selection, a digital signal to the digital input DI3 (terminal 10) controls
External Fault Close.
Index
P3.5.1.11
To change the input from DI3 to, for example, DI6 (terminal 16) on the standard I/O, obey
these instructions.
PROGRAMMING IN THE GRAPHICAL DISPLAY
1
Make a selection of a parameter. To go into the Edit
mode, push the arrow button Right.
10
Input type
Slot
(text dis-
play)
dI
A
dI
A
dI
A
dI
A
dI
A
dI
A
Parameter
Default
External fault
DigIN SlotA.3
close
Input #
Explanation
Digital input #1 (terminal 8) on a board in Slot A
1
(standard I/O board).
Digital input #2 (terminal 9) on a board in Slot A
2
(standard I/O board).
Digital input #3 (terminal 10) on a board in Slot
3
A (standard I/O board).
Digital input #4 (terminal 14) on a board in Slot
4
A (standard I/O board).
Digital input #5 (terminal 15) on a board in Slot
5
A (standard I/O board).
Digital input #6 (terminal 16) on a board in Slot
6
A (standard I/O board).
ID
405
STOP
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
PARAMETER DESCRIPTIONS
Description
OPEN = OK
CLOSED = External fault
READY
Digital inputs
ID:405
P3.5.1.7
Ext Fault Close
DigINSlotA3
Ext Fault Open
DigINSlot0.2
Fault Reset Close
DigINSlotA6
I/O