VACON · 130
PARAMETER DESCRIPTIONS
[Hz]
ID103, ID104
ID500
ID500
[t]
Fig. 21: The acceleration/deceleration curve (S-shaped)
P3.4.5 ACCELERATION TIME 2 (ID 502)
Use this parameter to set the time that is necessary for the output frequency to increase
from zero frequency to maximum frequency.
P3.4.6 DECELERATION TIME 2 (ID 503)
Use this parameter to set the time that is necessary for the output frequency to decrease
from maximum frequency to zero frequency.
P3.4.7 START MAGNETISING TIME (ID 516)
Use this parameter to set the time during which the DC current is fed to the motor before the
acceleration starts.
P3.4.8 START MAGNETISING CURRENT (ID 517)
Use this parameter to set the DC current that is fed into the motor at the start.
If the value of this parameter is set to 0, the Start Magnetising function is disabled.
P3.4.9 DC BRAKING TIME AT STOP (ID 508)
Use this parameter to set the braking is ON or OFF and to give the braking time when the
motor stops.
If the value of this parameter is set to 0, the DC Brake function is disabled.
P3.4.10 DC BRAKE CURRENT (ID 507)
Use this parameter to set the current that is fed into the motor during DC braking.
If the value of this parameter is set to 0, the DC Brake function is disabled.
10
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205