5.2

Periodic Inspection

The items that must be inspected one or two times every 6 months to 1 year are listed below. When the equipment is moved
or modified, or layout of the wiring is changed, also implement this inspection.
Item
Inspection item
1
Ambient
environment
2
Installation
3
Connection
4
Module diagnostics
*1 The temperature in the control panel where the Motion CPU module is installed is the ambient temperature.
*2 When an extended temperature range base unit is used, each module can be used in the environment of 0 to 60 (32 to 140).
5 INSPECTION AND MAINTENANCE
60
5.2 Periodic Inspection
Inspection
Ambient
Measure with a thermometer.
*1
temperature
Ambient humidity
Measure with a hygrometer.
Atmosphere
Measure corrosive gas.
Looseness, rattling
Move the module to check for
looseness and rattling.
Adhesion of dirt and
Visual inspection
foreign matter
Looseness of
Check for looseness of
terminal screws
terminal screws.
Proximity of
Visual inspection
solderless terminals
to each other
Looseness of
Visual inspection
connectors
Check with the module
diagnostics of GX Works3.
Criterion
Action
*2
0 to 55 (32 to 131)
Make sure the environment satisfies all
measurement criteria.
5 to 95%RH
No corrosive gases.
The module must be
Retighten the screws.
installed firmly.
If the modules are loose, fix it with screws.
Dirt and foreign matter
Remove dirt and foreign matter and clean.
must not be present.
Attach a connector cover to the connectors
that are not being used.
The connectors not being
used must have a cover
attached.
Screws must not be loose.
Retighten the terminal screws.
Solderless terminals must
Correct spacing as appropriate.
be properly spaced.
Connectors must not be
Insert the connector securely so there is no
loose.
looseness.
An error has not occurred.
Confirm details of the error, remove the error
factor.