Led Indications - Mitsubishi Electric QJ71DN91 User Manual

Melsec q series devicenet master-slave module
Hide thumbs Also See for QJ71DN91:
Table of Contents

Advertisement

5 SETUP AND PREPARATION

5.3.1 LED indications

QJ71DN91
RUN
MS
NS
ERR.
5 - 6
The following explains the names of the LEDs on the QJ71DN91 and their
indications in mode 0 to 8.
For the LED indications in mode 9 to C, refer to Section 5.4 Hardware Test or 5.6
Communication Test.
Table 5.1 LED names and indications
LED name
Color
RUN
Green
ERR.
Red
MS
Green
NS
Green
Red
Green/Red
LED status
ON: Operating normally
OFF: Watchdog timer error
ON: Node No. setting error
Flashing: Node number switch or mode switch was changed
during module operation.
ON: Communication is available.
Flashing: Parameter error
ON: Communication in progress
Flashing: Waiting for communication (waiting for I/O
communication request from programmable controller
CPU, or waiting for communication start of the target
module)
ON: Node No. duplication or bus off error (communication line
error)
Flashing: <In master function mode> A node that does not
respond exists.
<In slave function mode> Communication with the
master node is interrupted.
OFF: Power to the network is not being supplied.
MELSEC-Q
5 - 6

Advertisement

Table of Contents
loading

Table of Contents