4 FUNCTIONS
4 - 14
6)
If the parameter check has failed, the ERR. LED lights up and Error
Set Signal for Slave Function (X08) is set to on. At this time, I/O
Communicating (X01) is not set to on.
Check the error code in Error Information for Slave Function (address:
0601
), and take corrective actions.
H
7) Setting I/O Communication Request (Y11) to off stops I/O
communication with the master node, causing I/O Communicating
(X01) to turn off.
MELSEC-Q
4 - 14