10 TROUBLESHOOTING
Error
Detected
code
in:
(Hex.)
DNTMWR was not executed for three
sequence scans although "Data
21
QJ71DN91
H
consistency dedicated instruction setting
for master function" is enabled.
DNTSRD was not executed for three
sequence scans although "Data
22
QJ71DN91
H
consistency dedicated instruction setting
for slave function" is enabled.
DNTSWR was not executed for three
sequence scans although "Data
23
QJ71DN91
H
consistency dedicated instruction setting
for slave function" is enabled.
The master function is used but "Data
consistency dedicated instruction setting
24
QJ71DN91
H
for slave function" was enabled and I/O
communication was started.
The slave function is used but "Data
consistency dedicated instruction setting
25
QJ71DN91
H
for master function" was enabled and I/O
communication was started.
The number of slave function receive
80
QJ71DN91
H
bytes is out of range.
The number of slave function transmit
81
QJ71DN91
H
bytes is out of range.
Both of the slave function transmit and
82
QJ71DN91
H
receive bytes are set to 0.
When using both the master and slave
A0
QJ71DN91
functions, the number of I/O points is set
H
to 0 for both of them.
10 - 10
Description
Action
• Correct the sequence program so that
DNTMWR is executed in every scan.
• When not using Data consistency
dedicated instruction, disable "Data
consistency dedicated instruction setting
for master function", then turn on I/O
Communication Request (Y11).
• Correct the sequence program so that
DNTSRD is executed in every scan.
• When not using Data consistency
dedicated instruction, disable "Data
consistency dedicated instruction setting
for slave function", then turn on I/O
Communication Request (Y11).
• Correct the sequence program so that
DNTSWR is executed in every scan.
• When not using Data consistency
dedicated instruction, disable "Data
consistency dedicated instruction setting
for slave function", then turn on I/O
Communication Request (Y11).
• Disable "Data consistency dedicated
instruction setting for slave function", then
turn on I/O Communication Request
(Y11).
• Disable "Data consistency dedicated
instruction setting for master function",
then turn on I/O Communication Request
(Y11).
• Set it within the range of 0 to 128 bytes.
• Set it within the range of 0 to 128 bytes.
• Set either of the transmit or receive bytes
to any other than 0.
• Set I/O points of slave nodes in
Parameters for Master Function.
• Set transmit/receive bytes in Parameters
for Slave Function.
(Either of master or slave function values
must be set.)
MELSEC-Q
Detectability
Master
Slave
function
function
10 - 10