Technical Data Of Keb Combivert F5-Afe Devices; Table 18: Technical Data Of Keb Combivert F5-Afe Devices - KEB COMBIVERT F5 Instructions For Use Manual

Frequency converters
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

DIMENSIONING

9.3 Technical data of KEb COMbIVERT F5-AFE devices

Max. precharging AFE at an ambient temperature Ta = 45°C and Unmax = 440Vac /
480Vac. Corresponding higher charging currents are expected at higher mains voltages.
In this case please contact KEB!
Size
S
Cint
AFE
kVA
uF
14
11
820
16
23
1,260
18
35
1,800
20
52
3,900
22
80
4,950
24
125
8,250
26
173
11,700
27
208
14,100
28
256
19,800
29
319
19,800
30
395
39,600
33
554
59,400
34
616
39,600
38
1005 59,400
Legend
S
actual net
Cint
internal capacity
maximum, connectable capacity
Cextmax
R
Load-shunt
Option precharging resistance see chapter => 4.1.4.
1)
Table 18:
Technical data of KEB COMBIVERT F5-AFE devices
ATTENTION
Cextmax
(at
U=440Vac / 480Vac)
R
uF
20
10
20
40,000/35,000
2.5
40,000/35.000
2.5
35,000/30,000
2.5
33,000/27,000
2.5
30,000/24,000
2.5
27,000/20,000
5.8
27,000/20,000
5.8
140,000/110,000
5.8
1)
230,000/180,000
3.9
1)
140,000/110,000
5.8
1)
230,000/180,000
3.9
1)
A restart for AFE with NTC is allowed only after 5 minutes.
Max. external
Max. total
charging cur-
charging cur-
rent
rent
(at U=440Vac /
(at U=440Vac /
480Vac)
480Vac)
A
A
73 / 67
104
130 / 120
190
320 / 315
350
250/270
250/270
250/270
250/270
250/270
-
107/117
107/117
-
107/117
-
161/175
107/117
-
161/175
Notes
NTC as shunt
1)
1)
1)
1)
1)
59

Hide quick links: