INSTALLATION

5 Installation

5.1 EMC-compatible control cabinet installation

1a
Mains fuse
1b
Precharging fuse
2a
Pre-charging contactor
2b
Main contactor (before LCL filter)
3
EMC filter
4
AFE/LCL filter (if necessary integrat-
ed in 4)
5
COMBIVERT F5-AFE
5a
If necessary external load-shunt
6
External DC fuses
7
Drive converter
8
Motor line
9a
Power unit equipotential bonding
with the housing earth
9b
Protective Earth (PE) on the mount-
ing plate power circuit
9c
Protective Earth (PE) on the mount-
ing plate control circuit
10
Mains connection power circuit
10 A Mains connection control circuit
11
Control lines
Large area contact at the mounting
plate
Table 14:
EMC-compatible control cabinet installation

5.2 Installation instructions

34
11
10a
9c
Control circuit
Stationarily install and earth COMBIVERT.
Take care to prevent foreign material, dust, mist or water getting into the unit.
Allow for sufficient heat dissipation if installed in a dust-proof housing.
Install the COMBIVERT in an appropriate housing in accordance with the local reg-
ulations when operating it in explosion-endangered spaces.
Protect COMBIVERT against conductive and aggressive gases and liquids.
The AFE/LCL filter must be placed in the immediate environment of the AFE.
The drive converters must be placed in the immediate environment of the AFE.
The DC connection lines must be kept as short as possible.
The use of ferrite on the DC line is not permitted.
150 mm
3
2a
2b
1b
150 mm
4
1a
10
9b
Power circuit
150 mm
5a
7
5
30 mm
6
8
9a
Direction of the
cooling fins

Hide quick links:

Advertisement

Table of Contents
loading