6 Set up with the display and adjustment module
46
well as measured value and echo curve memory is deleted. The event
and parameter modification memories remain unaffected.
Basic settings: Resets the parameter settings, incl. special param-
eters, to the default values of the respective instrument. Any stored
false signal suppression or user programmable linearisation curve, as
well as the measured value memory, is deleted. Order-related settings
are not taken over into the current parameters after this reset.
The following table shows the scope of the reset function and the
default values of the instrument:
Menu
Menu item
Setup
Measurement
loop name
Units
Application
Min. adjustment
Max. adjustment
Damping
Current output
mode
Current output,
min./max.
Display
Displayed value 1 Filling height
Displayed value 2 Electronics temperature
Backlight
Additional adjust-
Date/Time
ments
Scaling size
Scaling format
Current output 1
and 2 size
Current output 1
and 2 adjustment
Linearisation
HART mode
Default value
Sensor
Distance in m
Temperature in °C
Medium: Water solution
Application: Storage tank
Vessel top: Dished form
Vessel bottom: Dished form
Vessel height/Measuring range: 30 m
30 m
0,000 m(d)
0.0 s
Output characteristics: 4 ... 20 mA
Fault mode: < 3.6 mA ▼
Min. current: 3.8 mA
Max. current: 20.5 mA
Switched on
Time format: 24 h
Volume
l
100.00 lin %, 100 l
0.00 lin %, 0 l
Lin %
100.00 %, 100 l
0.00 %, 0 l
Linear
HART address: 0
Loop current mode: Analogue cur-
rent output
VEGAPULS 64 • HART and accumulator pack