9 Diagnosis, asset management and service
Fault description
13. Measured value
jumps sporadically to-
wards 100 % during
emptying
Reaction after fault recti-
fication
24 hour service hotline
62
Error pattern
Cause
Varying condensation or con-
tamination on the antenna
0
time
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven
days a week around the clock.
Since we offer this service worldwide, the support is provided in
English. The service itself is free of charge, the only costs involved are
the normal call charges.
9.5

Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with ap-
propriate Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electron-
ics modules are adapted to the respective sensor and differ in signal
output or voltage supply.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
In the factory
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside
of the housing as well as on the delivery note.
When loading on site, the order data must first be downloaded from
the Internet (see operating instructions manual "Electronics module").
Caution:
All application-specific settings must be entered again. That's why you
have to carry out a fresh setup after exchanging the electronics.
If you saved the parameter settings during the first setup of the sen-
sor, you can transfer them to the replacement electronics module. A
fresh setup is then not necessary.
9.6

Software update

The following components are required to update the instrument
software:
Rectification
Carry out false signal suppres-
sion or increase false signal
suppression in the close range
by editing
With bulk solids, use radar sen-
sor with purging air connection
VEGAPULS 64 • HART and accumulator pack