Led Indicators; Buttons - ABB Conceptpower DPA 500 User Manual

Ups system 100 - 500 kw
Hide thumbs Also See for Conceptpower DPA 500:
Table of Contents

Advertisement

The 2 x 20 character LCD simplifies the communication with the UPS and provides the necessary monitoring
information about the UPS. The menu driven LCD enables the access to the:
Even register (event log)
Show measurements such as U, I, f, P, Q, S, load %, battery runtime and others
Perform commands like start-up and shut-down of UPS and others
Load transfer from INVERTER to BYPASS and vice-versa
Diagnosis (SERVICE MODE)
Adjustments and testing
6.5.1

LED Indicators

The mimic diagram serves to indicate the general status of the UPS. The LED-indicators show the power flow
status and in the event of mains failure or load transfer from inverter to bypass and vice-versa. The corresponding
LED-indicators will change colors from green (normal) to red (warning).
The LEDs LINE 1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply.
The LEDs INVERTER and BYPASS if green indicate which of the two is supplying power to the critical load. When
the battery is supplying the load due to mains failure the LED-indicator BATTERY is flashing.
The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the same time an
audible alarm will be activated.
INDICATOR
INDICATOR STATUS
ALARM
OFF
RED
LINE 1
GREEN
RED
LINE 2
GREEN
RED
OFF
BYPASS
GREEN
OFF
INVERTER
GREEN
RED
OFF
GREEN
BATTERY
RED
Flashing RED
Flashing GREEN
6.5.2

Buttons

The buttons allow the user to operate the UPS to perform settings and adjustments, to start-up and shutdown the
UPS, to monitor on the LCD display the voltages, currents, frequencies and other values.
BUTTON
FUNCTION
ON/OFF
ON/OFF
UP ()
DOWN ()
RESET
ENTER
MEANING
No alarm condition
Alarm condition
Mains rectifier available
Mains rectifier not available
Mains bypass available
Main bypass not ok or not available
UPS is turned off
Load on bypass (Bypass-or Eco-Mode)
Bypass not operating (switched-off)
Load on inverter
Inverter fault or load not transferable to inverter
Inverter not operating (switched-off)
Battery OK
Battery fault or battery is discharged
Battery in discharge and battery voltage critical or battery
fuse open
Battery in discharge and battery voltage good
By pressing both keys simultaneously it switches the UPS ON
By pressing both keys simultaneously it switches the UPS OFF (shutdown)
Move upwards through the menu
Increase values
Move downwards through the menu
decrease values
Cancel the audible alarm. If the alarm condition remains the LED will remain red
Return to previous menu
Confirms a chosen menu item
Confirms a chosen value
04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx
Modifications reserved
Page 45/78 ABB