On the Interface board are located two LED's:
Green LED showing the status of the Interface:
- Fast Blinking: 2 times/sec = Interface is Master (1
- Slow Blinking: 1 times/sec = Interface is Slave ( 2
Red LED Board Alarm (indicates a possible replacement of the board)
On the Master cabinet the following ports of the customer interface board are active:
The Input ports (X3)
The Output ports (X2)
The Interlock function (X1)
On the Salve cabinet(s) following ports of the customer interface board are active:
The Input ports (X3)
External Output Breaker (X2 9/10) and External Manual Bypass (X2 7/8)
All other ports on the Salve cabinet(s) are inactive.
5.3

JD1 / RS232 PC / Laptop Interface

The Computer Interface JD1 located on the distribution part is an intelligent RS 232 serial port that
allows the UPS system to be connected to a computer. The connector JD1 is a standard D-Type, 9-
pin, female.
It is used to download system event log and to make firmware upgrades.
5.4

USB PC / Laptop Interface

The Computer Interface USB has the same function as the RS 232 serial port JD1. Use either USB
or RS232 but not both at the same time.
5.5

JR2 / RS232 Interface for Multidrop

The Computer Interface JR2 (RJ 45 connector) located on the distribution part is the Multidrop
connection which is needed for multi-cabinet configurations. To enable the Multidrop communication
between cabinets it is necessary to set JP2 jumper correctly on the customer interface board as
shown in the table here below.
Customer Interface Board, PCB NW22085D (with ROM76-12) or NW22085E or later versions
First unit (Master)
Middle Unit (Slave)
Last Unit (Slave)
Note: on the (older) versions NW22085B/C without ROM76-12 make a bridge between X3-11
& X3-12.
Modifications reserved
Page 33/94
JP2 = OFF
JP2 = ON
JP2 = ON
Cabinet of a parallel System)
st
,.. 6
cabinet of a //- System)
nd
th