10.9 OPTIONS
- SNMP card and WaveMon Management Software , Modbus Protocol
- External Battery Cabinets
- In/Output Transformator for special voltages on request
- Temp. sensor for battery temp. control
10.9.1 SNMP card / WaveMon Management Software
The Simple Network Management Protocol (SNMP) is a worldwide-standardized communication-protocol. It is used
to monitor any device in the network via simple control language. The UPS-Management Software WaveMon also
provides its data in this SNMP format with its internal software agent. The operating system you are using must
support the SNMP protocol. We offer our WaveMon software with SNMP functionality for Novell, OS/2, all Windows
running on INTEL and ALPHA, DEC VMS, Apple.
Two types of SNMP interfaces with identical functionality are available: an external SNMP-Adapter (Box) and an
internal SNMP-Card. Both can manage a parallel system (N modules) and return either global values - which are
consistent for the whole parallel system - or specific values from the single modules.
Ethernet
10.10 BATTERY AUTONOMIES
10.10.1 Examples of Internal Battery Autonomy of DPA UPScale RI 11, RI 12, RI 22 , RI 24
Module Type
Internal Separate Battery configuration
Frame Type
Separate Battery / Module
UPScale RI 11
(1x40)x7Ah / Module
max. 40 blocks
1 modules ONLY
UPScale RI 22
(1x50)x7Ah / Module
max. 80 blocks
1 modules ONLY
UPScale RI 22
(1x40)x7Ah / Module
max. 80 blocks
up to 2 modules
Internal Common Battery configuration
Module Type
With 1 Module
Total System Power
UPScale RI 22
1x (2x40)x7Ah
Module Type
With 2 Modules
Total System Power
UPScale RI 22
1x (2x40)x7Ah
UPScale RI 24
2x (2x40)x7Ah
External SNMP-Adapter
Internal SNMP-Card
UPScale M 10
8kW
8
11
8
1 x UPScale M 10
8kW
21
2 x UPScale M 10
16kW
8
21
04-3006_S10_TDS_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc
Modifications reserved
UPS
9
Module need at least 48 blocks for full power
or minimum 40 blocks for 16kW
Battery Autonomy in (min.) per Module
10kW
12kW
6
5
8.
7
6
5
Battery Autonomy in (min.) for Tot. System Power
10kW
12kW
15
12
20kW
24kW
6
5
16
13
Section-10
UPScale M 20
16kW
20KW
4
1 x UPScale M 20
16kW
20KW
8
5
2 x UPScale M 20
32KW
40kW
9
5
Page 12/16 ABB