Scene Setup

Setting Zone Levels, Fade Rates, and Shade Group Actions

1. Enter programming mode.
Main menu
2. Use the Master buttons to highlight "Scene setup" and press
Timeclock
the OK button to accept.
Scene setup
3. Use the Master buttons to highlight "Levels" to adjust lighting
and/or shade levels. Press the OK button to accept. Use the
Master buttons to highlight the scene number of your desired
Scene setup
scene. Press the OK button to accept.
Levels
4. Set each zone to the desired light level for this scene using
the zone raise/lower buttons. The info screen will display the
Labels
zone and percentage as you adjust it.
To set a zone as unaffected, lower the light levels all the way
Scene setup
to off, then hold the zone lower button for 3 seconds. The
screen will display "---" and the three middle LEDs for the
zone will be lit to indicate this zone is unaffected by the scene
Scene 1
(the zone will not change when this scene is initiated).
When all zones are at the desired level, press the OK button to
accept.
Scene 1
5. Use the Master buttons to set the fade time for this scene.
Set zones
Press the OK button to accept.
6. Note: This step is applicable only if you have shades on your
3 seconds
system. If you do not have or do not wish to set shade groups
for this scene, press the OK button to skip this step.
Scene 1
Set each shade group to the desired level for this scene.
When all shade groups are at the desired level, press the OK
Adjust fade
button to accept.
3
seconds
For shade programming, see the full installation and operation
guide at www.lutron.com/qs.
7. The info screen will confirm that your scene has been saved.
Scene 1
8. Exit programming mode.
Set shade
Groups
Saved
®
3
1
9
2
10
11
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye QS with EcoSystem Control Unit Quick Installation and Operation Guide 17
5
4
12
13
6
14
7
15
8
16
1
9
1
9
Master
buttons
9-16
1-8
OK
OK
button
Timeclock
(back) button
2
10
3
11
4
12
5
13
6
14
7
Shade
button group
2
10
3
11
4
12
5
13
Zone raise
Zone lower
15
8
16
1
6
14

Advertisement

Chapters

Table of Contents
loading

Table of Contents