3.8 OFFSET screen
(1)
(2)
(3)
(4)
(1) Channel Selection Display : It is available for IPC5000D.
(2) PV Offset Display and Input : Compensate the offset value of analog input.
PV = Analog input + OFFSET
Range: -99.9 ~ +99.9
(3) Digital Filter Display and Input : The filter is used for preventing the quick change of
Range: 0.0 to 120sec(0.0 : Filter is OFF)
(4) Compensation: compensatory function for input(Analog input)
LIN(Biasing)
Apprx.(Approximation) is used to obtain capacity measurement signals when input signals
and required measurement signals do not have a linear relationship, such as with spherical
tank levels and capacities.
When 'SET' button is pressed, screen switches to the specified method setup screen
('COMPENSATE' screen)
OFFSET
EXIT
CH2
CH1
Unit : NONE
PV OFFSET
DIGITAL FILTER
COMPENSATE
RANGE
OFFSET
Fig. 3.8.1 OFFSET screen
analog input.
is used to correct input values affected by sensor deterioration.
2003.01.23
12H59M
9.9
sec
0.1
APPRX
LIN
SET
MODE
ALARM