Input type
K(CA)
J(IC)
R
Thermo
S
couple
B
E(CRC)
T(CC)
N
W1
W2
C
* FS : Full Scale
Input
Instrument input range
range
ºC
code
K1
-200.0~200.0
K2
0.0 ~ 1200.0
K3
0.0~800.0
K4
0.0~400.0
K5
0.0~1316.0
J
0.0~800.0
R
0.0~1600.0
S
0.0~1600.0
B
0.0~1800.0
E
0.0~800.0
T
-200.0~300.0
N
0.0~1300.0
W1
0.0~1200.0
W2
0.0~2300.0
C
0.0~2300.0
Measurement accuracy:
± 0.1% of span typical(± 1 digit for display)
ºF
-328.0~392.0
+/-0.1%FS
32.0~2192.0
+/-0.1%FS
32.0~1472.0
+/-0.1%FS
32.0~752.0
+/-0.1%FS
32.0~2400.0
+/-0.1%FS
32.0~1472.0
+/-0.1%FS
32.0~2912.0
+/-0.1%FS
32.0~2912.0
+/-0.1%FS
32.0~3272.0
+/-0.1%FS
32.0~1472.0
+/-0.1%FS
-328~572.0
+/-0.1%FS
32~2372
+/-0.1%FS
32~2192
+/-0.1%FS
32~4172
+/-0.1%FS
32~4172
+/-0.1%FS
- 22 -
Below 0ºC : +/-0.2%FS
+/-4.0%FS at 0 to 260ºC
+/-0.15%FS at 260 to 800ºC
+/-0.3%FS at –200 to -45ºC