Honeywell IPC5000 Installation Manual page 83

Universal programmable controller
Table of Contents

Advertisement

(4) RAMP UNIT type selection button
Selects the ramp type for program or fix control.
TIME: Sets the ramp by the hour unit. The slope is set by the difference ratio of the previous
target setting value and the current setting value. See the following figure.
SP
SLOPE: Sets the slope by the rate unit.
Input unit: SPU/MIN or SPU/SEC (SPU: Set Point Unit)
See the following figure.
SP
(5) LANGUAGE selection button
You can set or modify the language shown in the default menu and user interface screen.
Default = ENG (English)
KOR
ENG
(6) Digital output channel adjustment
For the asynchronous mode, 12 digital outputs are allocated by channel.
For the synchronous mode, the setting section will be hidden.
When allocating the digital outputs, the event setting section will appear as much as the number of
digital output allocation in the segment editing window, whereas 12 event sections appear in the fix
control setting screen. However, settings can be made according to channel allocation.
Slope setting time
Previous
target setting
Previous
target setting
Time unit (Button 3 in the figure 3.17.1)
CHN
ENG: English, KOR: Korean, CHN: Chinese (non-simplified)
Current
target setting
SPU/MIN or
SPU/SEC
- 73 -
Time
Current
target setting
Time