Input/output specifications
Items
Number of inputs
Type
Sampling cycle
Indication Accuracy
Analog
Cold junction accuracy
input
Input bias
Digital filter
Square-root Extraction
Compensation
Input count
Connectable output type
External
switch input
Allocation (Fixed)
Sampling cycle
Trouble messages
2 (Universal input)
TC: K, J, R, S, B, E, T, N ,W,C(JIS/IEC)
RTD: Pt100 (JIS/IEC), JPt100 (JIS)
Linear:
VOLTAGE 0~10V, 0~5V, 1~5V
CURRENT 0 ~ 20mA, 4 ~ 20mA
For detail, refer to Table 2.6.1
100 ms/channel
±0.1%FS±1digit (Accuracy is variable according to input type
or range.)
±1.0 ºC (±1.8 ºF) (under standard conditions)
-99.9 ~ +99.9 variable
0 ~ 120 sec (0: filter off)
Low-cutoff: 0.1~5.0% of input (in case of voltage input from
orifice or pressure sensor)
Linearity / Approximation
(1)Segment breakpoint: 1 to 10 of total range
(2)Compensation: -50.0~105.0% of CH1/2 PV input range
(3)Bias
Linearity
: -50.0~105.0% of CH1/2 PV input range span
Approximation: -50.0~105.0% of CH1/2 PV input range
12 points
No-Voltage contact (relay contact) and Open collector (sink
current toward 0V)
RUN/STOP, ADV, HOLD, Channel selection, Trouble inputs,
Program number (or detail, refer to Table 2.6.2)
100 ms
32 items
- 84 -