E. This controller is guaranteed by Honeywell to have a specific immunity level, in compliance with CE regulations, against irradiated and conducted electromagnetic disturbances. By irradiated electromagnetic disturbances we recommend to screen the controller with a metal screen connected to ground.
Icon 100 Series Refrigeration Controllers are designed to measure, display, and control the temperature of refrigeration cases and coldrooms. The Icon 100 Series are powered by AC 230 V, 50/60 Hz, and can read from two thermistor probes (thermostat and / or defrost probes), and has up to three relay outputs (compressor, defrost and fan).
ICON 100 SERIES USER GUIDE 3. TECHNICAL SPECIFICATIONS Part Number Housing Self extinguishing PC/ABS Power Supply AC 230Vac ~ 4VA 50/60 Hz Display 3 digits, 14.2 mm high green LED's Resolution C or one unit Accuracy ± 0.7% t.s. Probe Type...
ICON 100 SERIES USER GUIDE 4. INSTALLATION 4.1. Introduction The controller must be installed in a place where it is protected from extreme vibrations, impacts, water, corrosive gases, steam etc. and where temperature and humidity do not exceed the values given in the technical specification table (see page 6).
ICON 100 SERIES USER GUIDE 4.6. Fitting lcon is supplied in a panel-mount enclosure. While fitting the controller we recommend to leave enough room at the back in order to avoid compressing or excessively bending the cables. Overall instrument size and panel cut-out dimensions are given in the Fig.
ICON 100 SERIES USER GUIDE 5. CONTROLLER SET-UP 5.1. Front Panel The front panel, as shown in the figures below, includes 4 keys, i.e., the UP key (increase), the DOWN key (decrease), the SET key (setting), the MANUAL DEFROST key, and a three-digit display with three signal LEDs: DP1, DP2, and DP3.
ICON 100 SERIES USER GUIDE 5.3. Display Functions As well as the temperature value display during normal functioning, the display also shows the value of the main setpoint and the configuration parameter values, as well as the codes of the latter and possible error messages.
ICON 100 SERIES USER GUIDE Note: In order to leave a configuration parameter unaltered during the modification procedure, depress the SET key, after having stored the modified value of the previous parameter, the controller displays the code of the parameter to be left unaltered.
ICON 100 SERIES USER GUIDE 5.10. Setting the Daily Defrost Cycles on the Real Time Clock It is possible to set-up 4 defrost cycles per day on Icon models: ICON-111SR, ICON-112SR & ICON-132SR. The time parameters regarding this function are d30, d31, d32 & d33 (See Section 6, Table 2).
ICON 100 SERIES USER GUIDE 6. PARAMETER CONFIGURATION The configuration parameters and related limits or options are given in the table below. A box without a ‘ ’ symbol means that the corresponding controller does not have that parameter. PARA-...
ICON 100 SERIES USER GUIDE 7. PARAMETER DESCRIPTION d1 Main setpoint: The controller Temperature at which the compressor is switched on. This must be fixed within the limits set in parameters d3 and d4. d2 Differential (hysteresis): The differential is the temperature added to the set point at which the compressor is switched off.
Page 16
ICON 100 SERIES USER GUIDE d16 Fan activation delay at controller start-up and defrost-end: This parameter sets the time interval that starts at controller start-up or at the end of a defrost cycle, during which the fan must remain off in order to not introduce warm and humid air into the case or coldroom (only for model ICON-132S &...
ICON 100 SERIES USER GUIDE 8. CONNECTING TO HONEYWELL GENUS NETWORK ® ® The Icon controller has an optional Genus communication module (Part Number: ® ICON-COMMS) which allows logging onto a Genus network for remote alarm monitoring and defrost control.
ICON 100 SERIES USER GUIDE 9. PROGRAMMABLE HOTKEY The Icon controller has an optional programmable HotKey (Part Number: ICON- KEY1). When the controller is switched ON, it is possible to upload the parameter configurations of the controller to the HotKey, or vice-versa to download parameter configurations from the HotKey to the controller.
ICON 100 SERIES USER GUIDE TROUBLESHOOTING (ERROR MESSAGES) Error messages are given in the table below. MESSAGE (BLINKING) DISPLAY CAUSE OUTPUTS Over temperature alarm. The case Active alarm output. Other / coldroom temperature exceeds outputs not modified d1+d6 and therefore always...
ICON 100 SERIES USER GUIDE APPENDIX 11.1. Appendix A – Default Factory Setting Parameters The following parameters are for values that are based on a stand-alone controller being used for a high temp application (dairy produce, fresh meat, chilled drinks etc.), with electric defrost.
Page 21
ICON 100 SERIES USER GUIDE EN2B-0002UK07 R0404...
Page 22
ICON 100 SERIES USER GUIDE EN2B-0002UK07 R0404...
Page 23
ICON 100 SERIES USER GUIDE EN2B-0002UK07 R0404...
Page 24
Automation & Control Solutions Cooling & Refrigeration Newhouse Industrial Estate Motherwell North Lanarkshire, ML1 5SB Scotland, United Kingdom Phone: (44) 01698 481698 Fax: (44) 01698 481699 www.honeywell.com/cooling Subject to change without notice. Printed in United Kingdom EN2B-0002UK07 R0404...