Settings in the slave station
Connect the engineering tool to the remote head module of remote head No.1 and set parameters.
In a redundant system, also write the same parameters to remote head No.2.
1.
Set the remote head module as follows.
[Project]  [New]
2.
Set the remote head No.2 remote head module for slot No.0 in the I/O assignment setting.
[Navigation window]  [Parameter]  [System Parameter]  [I/O Assignment] tab  [I/O Assignment Setting]
3.
Set the items in "Network Required Setting" of "CPU Parameter" as follows.
[Navigation window]  [Parameter]  [RJ72GF15-T2 (SR)]  [CPU Parameter]  [Network Required Setting]
4.
Set the module parameter of the module mounted on the remote head module. ( Manual for the module used)
5.
Write the set parameters to the remote head No.1 and remote head No.2 remote head modules, and reset or powering
off and on the remote head No.1 and remote head No.2 remote head modules.
[Online]  [Write to PLC]
In this setting example, default settings are used for the parameters other than those described. For the
parameter setting, refer to following. ( Page 76 PARAMETER SETTINGS)