Remote operation
For remote operations from the CC-Link IE Field Network diagnostics, follow the steps below.
*1 To perform remote RESET, preset "Remote Reset Setting" under "Operation Related Setting" of "CPU Parameter" to "Enable".
For details on the remote operations, refer to the following.
Page 27 Remote Operation
Station number setting of the remote head module
For the station number setting of the remote head module using the CC-Link IE Field Network diagnostics, follow the steps
below.
1.
Start the CC-Link IE Field Network diagnostics from the engineering tool connected to the master station.
2.
Select the icon of the remote head module with no station number setting from the network map window.
3.
Click the [Set Station No.] button in "Selected Station Communication Status Monitor".
4.
Set the station number in the following window, and click the [OK] button.
When the station number setting of the remote head module is performed from the master station of the
MELSEC-Q/L series, use the master/local module with a serial number (first five digits) of "13032" or later and
GX Works2 with Version 1.53F or later.
■Precautions
• The network number will be the same as that of the master station.
• When a network number and a station number are set in the "Network Required Setting" tab of "CPU Parameter", the
parameter settings take priority.
4 TROUBLESHOOTING
96
4.4 Checking the Network Status
1.
Select the module where the remote operations are
performed in the CC-Link IE Field Network diagnostics.
2.
Click the [Remote Operation] button in the "CC-Link IE
Field Diagnostics" window. Or right-click a module icon
in the "Network Status" and click [Remote Operation].
"Remote Operation" window is displayed.
3.
Select a remote operation (RUN, STOP, or RESET) to
be performed in "Operation".
4.
Click the [Execute] button to perform the remote
operation.