8.
User information setting
Set the user information for the SIL2 Process CPU and the project of both systems. ( GX Works3 Operating Manual)
9.
Creation of a program
Create a safety program and a standard program.
10.
Writing of data to the programmable controller
Write the parameters set by the engineering tool and the programs created above to both systems. ( MELSEC iQ-R CPU
Module User's Manual (Application))
11.
Reset of the SIL2 Process CPU
Restart both systems by either of the following methods.
• Turning off and on the power.
• Reset of the SIL2 Process CPU
12.
Check of the LED on the SIL2 Process CPU
Check that the LED on each module is in the following state. The CARD READY LED turns on or off according to whether an
SD memory card has been installed or not.
• Control system
*1
• Standby system
*1 The MST LED on the standby system RJ71GF11-T2 flashes in a redundant master station system.
The following LEDs turn on in the event of an error. Check the details of the error using the engineering tool, and eliminate the
error cause.
• SIL2 Process CPU: ERROR LED ( MELSEC iQ-R CPU Module User's Manual (Startup))
• SIL2 function module: ERROR LED ( MELSEC iQ-R CPU Module User's Manual (Startup))
• Redundant function module: ERR LED, L ERR LED ( MELSEC iQ-R CPU Module User's Manual (Startup))
• RJ71GF11-T2: ERR LED, L ERR LED ( MELSEC iQ-R Ethernet/CC-Link IE User's Manual (Startup))
1 FUNCTIONS
70
1.9 Safety Communication Relay Function