6.
Writing to the remote head module
Write the parameters set by the engineering tool to the remote head module. ( MELSEC iQ-R CC-Link IE Field Network
Remote Head Module User's Manual (Startup))
7.
Reset of the remote head module
Restart the system of the remote head module using either of the following methods.
• Turning off and on the power.
• Resetting the remote head module ( MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual
(Startup))
Procedures for the SIL2 Process CPU
1.
Power-on of the system
Before turning on the power, check the following items for both systems.
• The power supply is connected properly.
• The power supply voltage meets the specifications.
• The SIL2 Process CPU is in the STOP state.
After turning on the power, check that the following LEDs are turned on.
• Power supply module: POWER LED
• SIL2 Process CPU: READY LED
• SIL2 function module: READY LED
• Redundant function module: RUN LED
• RJ71GF11-T2: RUN LED
Although the LED on each module will be in the following state, proceed to the next step.
• SIL2 Process CPU: ERROR LED flashes.
• SIL2 function module: ERROR LED flashes.
• Redundant function module: ERR LED turns on.
• RJ71GF11-T2: ERR LED turns on.
2.
Creation of a project
Start the engineering tool and create a project. ( MELSEC iQ-R CPU Module User's Manual (Application))
3.
Connection between a personal computer and the SIL2 Process CPU
Connect a personal computer with the engineering tool installed to the SIL2 Process CPU. ( MELSEC iQ-R CPU Module
User's Manual (Application))
4.
Initialization of the SIL2 Process CPU
Initialize the SIL2 Process CPU using the engineering tool.
After initializing one SIL2 Process CPU, connect the other SIL2 Process CPU to the personal computer. After the connection,
initialize the SIL2 Process CPU using the engineering tool.
5.
Parameter setting for the SIL2 Process CPU
Set the system parameters, CPU parameters, and module parameters of each module. ( MELSEC iQ-R CC-Link IE Field
Network User's Manual (Application))
The system parameters can be set by loading the actual system configuration into the module configuration
diagram using the engineering tool.
6.
Safety communication setting
Set the safety communication. ( MELSEC iQ-R CC-Link IE Field Network User's Manual (Application))
7.
Writing of the system A/B setting
Set the system A/B setting using the engineering tool. ( MELSEC iQ-R CPU Module User's Manual (Application))
1 FUNCTIONS
1.9 Safety Communication Relay Function
1
69